- IEC 61850 server: unselect control when oper is not accepted

- IEC 61850 server: send select-failed for control when origin parameter is not valid
pull/228/head
Michael Zillgith 6 years ago
parent 4dede9b8a1
commit 4aaced2639

@ -1435,6 +1435,13 @@ Control_writeAccessControlObject(MmsMapping* self, MmsDomain* domain, char* vari
if (checkValidityOfOriginParameter(origin) == false) {
indication = DATA_ACCESS_ERROR_OBJECT_VALUE_INVALID;
ControlObject_sendLastApplError(controlObject, connection, "SBOw", CONTROL_ERROR_NO_ERROR,
ADD_CAUSE_SELECT_FAILED, ctlNum, origin, true);
if (DEBUG_IED_SERVER)
printf("IED_SERVER: SBOw - invalid origin value\n");
goto free_and_return;
}
@ -1571,6 +1578,8 @@ Control_writeAccessControlObject(MmsMapping* self, MmsDomain* domain, char* vari
CONTROL_ERROR_NO_ERROR, ADD_CAUSE_INCONSISTENT_PARAMETERS,
ctlNum, origin, true);
unselectObject(controlObject);
goto free_and_return;
}
}
@ -1654,6 +1663,9 @@ Control_writeAccessControlObject(MmsMapping* self, MmsDomain* domain, char* vari
setOpRcvd(controlObject, false);
abortControlOperation(controlObject);
if ((controlObject->ctlModel == 2) || (controlObject->ctlModel == 4))
unselectObject(controlObject);
}
}