- IEC 61850 server: control module return AddCause command-already-in-execution when second operate is received while command is executed

pull/246/head
Michael Zillgith 5 years ago
parent ede2c7766c
commit 5f02ea1661

@ -1783,6 +1783,18 @@ Control_writeAccessControlObject(MmsMapping* self, MmsDomain* domain, char* vari
goto free_and_return;
}
else if ((state == STATE_OPERATE) || (state == STATE_WAIT_FOR_EXECUTION)) {
if (DEBUG_IED_SERVER)
printf("IED_SERVER: Oper failed - control already being executed!\n");
indication = DATA_ACCESS_ERROR_TEMPORARILY_UNAVAILABLE;
ControlObject_sendLastApplError(controlObject, connection, "Oper",
CONTROL_ERROR_NO_ERROR, ADD_CAUSE_COMMAND_ALREADY_IN_EXECUTION,
ctlNum, origin, true);
goto free_and_return;
}
}
else if (strcmp(varName, "Cancel") == 0) {
if (DEBUG_IED_SERVER)

Loading…
Cancel