- IEC 61850 server: control - unselect when operate with wrong origin parameters, check if check parameter matches for SBO

pull/228/head
Michael Zillgith 6 years ago
parent 0ba4a70d33
commit c7f7989b85

@ -1145,11 +1145,13 @@ ControlObject_sendLastApplError(ControlObject* self, MmsServerConnection connect
}
static void
updateControlParameters(ControlObject* controlObject, MmsValue* ctlVal, MmsValue* ctlNum, MmsValue* origin)
updateControlParameters(ControlObject* controlObject, MmsValue* ctlVal, MmsValue* ctlNum, MmsValue* origin, bool synchroCheck, bool interlockCheck)
{
MmsValue_update(controlObject->ctlVal, ctlVal);
MmsValue_update(controlObject->ctlNum, ctlNum);
MmsValue_update(controlObject->origin, origin);
controlObject->synchroCheck = synchroCheck;
controlObject->interlockCheck = interlockCheck;
if (controlObject->ctlNumSt)
MmsValue_update(controlObject->ctlNumSt, ctlNum);
@ -1467,12 +1469,12 @@ Control_writeAccessControlObject(MmsMapping* self, MmsDomain* domain, char* vari
/* opRcvd must not be set here! */
bool interlockCheck = MmsValue_getBitStringBit(check, 1);
bool synchroCheck = MmsValue_getBitStringBit(check, 0);
bool testCondition = MmsValue_getBoolean(test);
controlObject->addCauseValue = ADD_CAUSE_SELECT_FAILED;
updateControlParameters(controlObject, ctlVal, ctlNum, origin);
updateControlParameters(controlObject, ctlVal, ctlNum, origin, interlockCheck, synchroCheck);
if (controlObject->checkHandler != NULL) { /* perform operative tests */
@ -1528,6 +1530,15 @@ Control_writeAccessControlObject(MmsMapping* self, MmsDomain* domain, char* vari
if (checkValidityOfOriginParameter(origin) == false) {
indication = DATA_ACCESS_ERROR_OBJECT_VALUE_INVALID;
if ((controlObject->ctlModel == 2) || (controlObject->ctlModel == 4)) {
ControlObject_sendLastApplError(controlObject, connection, "Oper",
CONTROL_ERROR_NO_ERROR, ADD_CAUSE_INCONSISTENT_PARAMETERS,
ctlNum, origin, true);
unselectObject(controlObject);
}
goto free_and_return;
}
@ -1570,7 +1581,10 @@ Control_writeAccessControlObject(MmsMapping* self, MmsDomain* domain, char* vari
if (controlObject->ctlModel == 4) { /* select-before-operate with enhanced security */
if ((MmsValue_equals(ctlVal, controlObject->ctlVal) &&
MmsValue_equals(origin, controlObject->origin) &&
MmsValue_equals(ctlNum, controlObject->ctlNum)) == false)
MmsValue_equals(ctlNum, controlObject->ctlNum) &&
(controlObject->interlockCheck == interlockCheck) &&
(controlObject->synchroCheck == synchroCheck)
) == false)
{
indication = DATA_ACCESS_ERROR_TYPE_INCONSISTENT;
@ -1585,7 +1599,7 @@ Control_writeAccessControlObject(MmsMapping* self, MmsDomain* domain, char* vari
}
}
updateControlParameters(controlObject, ctlVal, ctlNum, origin);
updateControlParameters(controlObject, ctlVal, ctlNum, origin, synchroCheck, interlockCheck);
MmsValue* operTm = getOperParameterOperTime(value);