Michael Zillgith
|
29efa333f8
|
- IEC 61850 server: allow server to start without logical devices in data model (#218)
|
6 years ago |
Michael Zillgith
|
cb8f159914
|
- IEC 61850 server: unbuffered reporting - send first integrity report after integrity timeout (before it was sent when the RCB was enabled)
|
6 years ago |
Michael Zillgith
|
c7f7989b85
|
- IEC 61850 server: control - unselect when operate with wrong origin parameters, check if check parameter matches for SBO
|
6 years ago |
Michael Zillgith
|
0ba4a70d33
|
- IEC 61850 server: fixed missing report timestamp update for unbuffered reporting
|
6 years ago |
Michael Zillgith
|
09b23aaa74
|
- IEC 618580 server: Added function IedServer_setServerIdentity to set values for MMS identity service
|
6 years ago |
Michael Zillgith
|
ae07c77d39
|
- CDC helpers: added functions to create ISC and BAC CDCs
|
6 years ago |
Michael Zillgith
|
2dba040c1a
|
- CDC helper functions: added stSeld and attributes from ControlTestingCDC to control CDCs
|
6 years ago |
Michael Zillgith
|
4aaced2639
|
- IEC 61850 server: unselect control when oper is not accepted
- IEC 61850 server: send select-failed for control when origin parameter is not valid
|
6 years ago |
Michael Zillgith
|
d8153483b5
|
- IEC 61850 server: fixed control handling to comply with test case sCtl25
|
6 years ago |
Michael Zillgith
|
3a248a4f20
|
- IEC 61850 server: fixed control handling to comply with test case sCtl11
|
6 years ago |
Michael Zillgith
|
0c83507727
|
- IEC 61850 server: pass origin, ctlNum, ctlVal to select handler for SBOw
|
6 years ago |
Michael Zillgith
|
abcf93416f
|
- added function IedServer_getNumberOfOpenConnections
- IEC 61850/MMS server: refactored connection handling
|
6 years ago |
Michael Zillgith
|
df0e7c08df
|
- IEC 61850 server: fixed new memory leak in unbuffered reporting
|
6 years ago |
Michael Zillgith
|
8991954e3c
|
- removed header dependencies from API headers
|
6 years ago |
Michael Zillgith
|
18c2e30f87
|
- IEC 61850 server: refactored reporting module; unbuffered reports are stored to report buffer and sent by connection handling thread
|
6 years ago |
Michael Zillgith
|
925c19bff6
|
- IED Server: added support for transient data objects
|
6 years ago |
Michael Zillgith
|
6c53924c05
|
- added additional length check in BerDecoder_decodeLength and checked return values in callers (fix problem #196)
|
6 years ago |
Michael Zillgith
|
8c1b75b382
|
- code cleanup; fixed issues from compiler warnings
|
6 years ago |
Michael Zillgith
|
6cbadb4b45
|
- IED server: added new function ControlAction_isSelect
|
6 years ago |
Michael Zillgith
|
5fbb67c44c
|
- some code beautification
|
6 years ago |
Michael Zillgith
|
6738215c8f
|
Merge pull request #183 from kiraly533/v1.4
TimeActivatedControl before wait check and fixes for file-upload issues.
|
6 years ago |
Michael Zillgith
|
5bd03b0611
|
- IED server: added function ConfigFileParser_createModelFromConfigFileEx with filename as argument to avoid dependency on FileSystem_... functions
- .NET projects: changed target framework of some project files to v4.0
|
6 years ago |
Király Péter
|
7ed8516344
|
Added getter for the time of the timeActivated controls.
|
6 years ago |
Király Péter
|
a39397d21d
|
Add check call before starting a timeactivated operate, so operates can be denied before the waiting state
|
6 years ago |
Michael Zillgith
|
69729bd8a0
|
- fixed - misspelled function name #180
|
6 years ago |
Michael Zillgith
|
e4c3875e3e
|
IEC 61850 server: added function ControlAction_getCtlNum to access ctlNum value inside control handlers
|
6 years ago |
Michael Zillgith
|
6b2404e80b
|
- GOOSE: option to enable/disable VLAN tagging
- IED Server: Allow setting different interfaces for different GOOSE publishers
|
6 years ago |
Michael Zillgith
|
2cf288fbeb
|
Merge branch 'v1.4' of https://github.com/mz-automation/libiec61850 into v1.4
|
6 years ago |
Michael Zillgith
|
57f6df3c3a
|
- HAL(Socket): Added function Socket_getLocalAddress
- IEC 61850 server: Added function ClientConnection_getLocalAddress
|
6 years ago |
Michael Zillgith
|
4c123c0c3c
|
- MMS server: fixed potential deadlock in multi-thread mode
|
6 years ago |
Michael Zillgith
|
d4304e0a38
|
- IEC 61850 server: URCB will not release reservation (and owner) when RCB is disabled
|
6 years ago |
Michael Zillgith
|
2e9761c541
|
- IED server: cancel outstanding control tasks when client closes connection (to prevent blocking the connection for waiting time activated controls)
|
6 years ago |
Michael Zillgith
|
7cb69c983a
|
- additionally allow comma and space as separators in ap-titles used in API functions
|
6 years ago |
Michael Zillgith
|
6c14425ca8
|
- IEC 61850 server: refactored control model API (changed handler signatures, added ControlAction object to access origin and set addCause value, ...)
- IEC 61850 client: added ControlObjectClient_getLastError function
|
6 years ago |
Michael Zillgith
|
28e2acbd33
|
- IED server: avoid dynamic memory allocation in control module
|
6 years ago |
Michael Zillgith
|
f0df571f42
|
- IED server: made code compatible with C++
|
6 years ago |
Michael Zillgith
|
a9fa07a7d4
|
- IED server: some memory optimizations in control module
|
6 years ago |
Michael Zillgith
|
2911781070
|
- IEC 61850 server/reporting: fixed bug when checking for invalid data set member
|
6 years ago |
Michael Zillgith
|
38d67a4e69
|
- IEC 61850 server/reporting: send access error "object-value-invalid"
when data attribute in report data set has no value
|
6 years ago |
Michael Zillgith
|
ebc71d9731
|
- IEC 61850 common: moved some internal code to better seperate
client/server side code
|
6 years ago |
Michael Zillgith
|
16c061b4df
|
- MMS server API: removed dependency from internal header file iso_server.h
|
6 years ago |
Michael Zillgith
|
d376370aaa
|
- IEC 61850 server: control model - implemented automatic handling of opRcvd, opOk, and tOpOk when present in data object
|
7 years ago |
Michael Zillgith
|
a3c2c4652e
|
- IEC 61850 server: control model - implemented automatic handling of stSeld when present in data object
|
7 years ago |
Michael Zillgith
|
c98a2b0baa
|
- MMS server: fixed connection handling problem in multi-threaded mode
|
7 years ago |
Michael Zillgith
|
994484d1a6
|
- MMS server: added semaphore for open connections map to prevent problem in multi-threaded mode
|
7 years ago |
Michael Zillgith
|
f2c811c7c7
|
- IedServer: fixed potential deadlock when IedServer_stop is directly called after IedServer_start
|
7 years ago |
Michael Zillgith
|
b35a566145
|
- IEC 61850 server: fixed problem in report module
|
7 years ago |
Michael Zillgith
|
0dff4286aa
|
- merged latest changes to the server reporting module from 1.3 branch
- merged with 1.3 branch
|
7 years ago |
Michael Zillgith
|
732ad79070
|
- fixed problem with read access to GCB (see github #130)
|
7 years ago |
Michael Zillgith
|
199d091c6d
|
- IEC 61850 server: don't send bufOvfl for unbuffered reports (see #101)
|
7 years ago |