<?xml version="1.0" encoding="UTF-8"?>
<!-- edited with XMLSPY v5 rel. 4 U (http://www.xmlspy.com) by Christoph Brunner (ABB Switzerland Ltd) -->
<SCL xmlns="http://www.iec.ch/61850/2003/SCL" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation="http://www.iec.ch/61850/2003/SCL
SCL.xsd">
<Header id="9-2LE-Spec" nameStructure="FuncName" version="0.7" revision="1"/>
<Communication>
<SubNetwork name="subnetwork1" type="8-MMS">
<Text>Station bus</Text>
<BitRate unit="b/s">10</BitRate>
<ConnectedAP iedName="TEMPLATE" apName="accessPoint1">
<Address>
<P type="IP">10.0.0.2</P>
<P type="IP-SUBNET">255.255.255.0</P>
<P type="IP-GATEWAY">10.0.0.1</P>
<P type="OSI-TSEL">0001</P>
<P type="OSI-PSEL">00000001</P>
<P type="OSI-SSEL">0001</P>
</Address>
<SMV ldInst="MUnn" cbName="MSVCB01">
<Address>
<P type="VLAN-ID">1</P>
<P type="VLAN-PRIORITY">4</P>
<P type="MAC-Address">01-0c-cd-04-00-01</P>
<P type="APPID">1001</P>
</Address>
</SMV>
</ConnectedAP>
</SubNetwork>
</Communication>
<Substation name="">
<VoltageLevel name="">
<Bay name="">
<ConductingEquipment name="Inn" type="CTR">
<SubEquipment name="A" phase="A">
<LNode lnClass="TCTR" lnInst="1"/>
</SubEquipment>
<SubEquipment name="B" phase="B">
<LNode lnClass="TCTR" lnInst="2"/>
</SubEquipment>
<SubEquipment name="C" phase="C">
<LNode lnClass="TCTR" lnInst="3"/>
</SubEquipment>
<SubEquipment name="N" phase="N">
<LNode lnClass="TCTR" lnInst="4"/>
</SubEquipment>
</ConductingEquipment>
<ConductingEquipment name="Unn" type="VTR">
<SubEquipment name="A" phase="A">
<LNode lnClass="TVTR" lnInst="1"/>
</SubEquipment>
<SubEquipment name="B" phase="B">
<LNode lnClass="TVTR" lnInst="2"/>
</SubEquipment>
<SubEquipment name="C" phase="C">
<LNode lnClass="TVTR" lnInst="3"/>
</SubEquipment>
<SubEquipment name="N" phase="N">
<LNode lnClass="TVTR" lnInst="4"/>
</SubEquipment>
</ConductingEquipment>
</Bay>
</VoltageLevel>
</Substation>
<IED name="TEMPLATE">
<AccessPoint name="accessPoint1">
<Server>
<Authentication/>
<LDevice inst="MUnn">
<LN0 lnType="9-2LELLN0" lnClass="LLN0" inst="">
<DataSet name="PhsMeas1">
<FCDA lnClass="TCTR" ldInst="1" fc="MX" doName="Amp"/>
<FCDA lnClass="TCTR" ldInst="2" fc="MX" doName="Amp"/>
<FCDA lnClass="TCTR" ldInst="3" fc="MX" doName="Amp"/>
<FCDA lnClass="TCTR" ldInst="4" fc="MX" doName="Amp"/>
<FCDA lnClass="TVTR" ldInst="1" fc="MX" doName="Vol"/>
<FCDA lnClass="TVTR" ldInst="2" fc="MX" doName="Vol"/>
<FCDA lnClass="TVTR" ldInst="3" fc="MX" doName="Vol"/>
<FCDA lnClass="TVTR" ldInst="4" fc="MX" doName="Vol"/>
</DataSet>
<SampledValueControl name="MSVCB01" datSet="PhsMeas1" smvID="xxxxMUnn01"
smpRate="80" nofASDU="1" confRev="1">
<SmvOpts refreshTime="false" sampleSynchronized="true"
security="false" dataRef="false"/>
</SampledValueControl>
</LN0>
<LN lnType="9-2LETCTR" lnClass="TCTR" inst="1"/>
<LN lnType="9-2LETCTR" lnClass="TCTR" inst="2"/>
<LN lnType="9-2LETCTR" lnClass="TCTR" inst="3"/>
<LN lnType="9-2LETCTR" lnClass="TCTR" inst="4"/>
<LN lnType="9-2LETVTR" lnClass="TVTR" inst="1"/>
<LN lnType="9-2LETVTR" lnClass="TVTR" inst="2"/>
<LN lnType="9-2LETVTR" lnClass="TVTR" inst="3"/>
<LN lnType="9-2LETVTR" lnClass="TVTR" inst="4"/>
</LDevice>
</Server>
</AccessPoint>
</IED>
<DataTypeTemplates>
<LNodeType id="9-2LELLN0" lnClass="LLN0">
<DO name="Mod" type="9-2LEINC"/>
</LNodeType>
<LNodeType id="9-2LETCTR" lnClass="TCTR">
<DO name="Amp" type="9-2LESAVAmp"/>
</LNodeType>
<LNodeType id="9-2LETVTR" lnClass="TVTR">
<DO name="Vol" type="9-2LESAVVol"/>
</LNodeType>
<DOType id="9-2LESAVAmp" cdc="SAV">
<DA name="instMag" bType="Struct" type="9-2LEAV" fc="MX"/>
<DA name="q" bType="Quality" fc="MX"/>
<DA name="sVC" bType="Struct" type="9-2LEsVCAmp" fc="CF"/>
</DOType>
<DOType id="9-2LESAVVol" cdc="SAV">
<DA name="instMag" bType="Struct" type="9-2LEAV" fc="MX"/>
<DA name="q" bType="Quality" fc="MX"/>
<DA name="sVC" bType="Struct" type="9-2LEsVCVol" fc="CF"/>
</DOType>
<DOType id="9-2LEINC" cdc="INC">
<DA name="ctlVal" fc="CO" bType="INT32"/>
<DA name="stVal" fc="ST" bType="INT32" dchg="true"/>
<DA name="q" fc="ST" bType="Quality" dchg="true"/>
<DA name="t" fc="ST" bType="Timestamp" dchg="true"/>
</DOType>
<DAType id="9-2LEAV">
<BDA name="i" bType="INT32"/>
</DAType>
<DAType id="9-2LEsVCAmp">
<BDA name="scaleFactor" bType="FLOAT32">
<Val>0.001</Val>
</BDA>
<BDA name="offset" bType="FLOAT32">
<Val>0</Val>
</BDA>
</DAType>
<DAType id="9-2LEsVCVol">
<BDA name="scaleFactor" bType="FLOAT32">
<Val>0.01</Val>
</BDA>
<BDA name="offset" bType="FLOAT32">
<Val>0</Val>
</BDA>
</DAType>
</DataTypeTemplates>