You cannot select more than 25 topics Topics must start with a letter or number, can include dashes ('-') and can be up to 35 characters long.
libiec61850/tools/model_generator/inverter_with_report.icd

271 lines
10 KiB
XML

This file contains ambiguous Unicode characters!

This file contains ambiguous Unicode characters that may be confused with others in your current locale. If your use case is intentional and legitimate, you can safely ignore this warning. Use the Escape button to highlight these characters.

<?xml version="1.0" encoding="UTF-8"?>
<SCL xmlns="http://www.iec.ch/61850/2003/SCL">
<IED name="ied1">
<Services>
<DynAssociation />
<GetDirectory />
<GetDataObjectDefinition />
<GetDataSetValue />
<DataSetDirectory />
<ReadWrite />
<GetCBValues />
<ConfLNs fixPrefix="true" fixLnInst="true" />
</Services>
<AccessPoint name="accessPoint1">
<Server>
<Authentication password="true" />
<LDevice inst="Inverter">
<LN0 lnClass="LLN0" lnType="LLN02" inst="">
<DataSet name="dataset1" desc="">
<FCDA ldInst="Inverter" lnClass="LLN0" fc="ST" doName="Mod" daName="q" />
<FCDA ldInst="Inverter" lnClass="MMXU" fc="ST" lnInst="1" doName="Mod" daName="q" />
<FCDA ldInst="Inverter" lnClass="MMXU" fc="CF" lnInst="1" doName="Mod" daName="ctlModel" />
</DataSet>
<ReportControl name="rcb1" confRev="0" datSet="dataset1" rptID="ID" intgPd="0" bufTime="0">
<TrgOps dchg="true" qchg="true" />
<OptFields />
</ReportControl>
<DOI name="Mod">
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
</LN0>
<LN lnClass="LPHD" lnType="LPHD2" inst="1" prefix="" />
<LN lnClass="ZINV" lnType="ZINV3" inst="1" prefix="">
<DOI name="Mod">
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="vendor">
<Val>MegaSolar</Val>
</DAI>
</DOI>
</LN>
<LN lnClass="MMXU" lnType="MMXU1" inst="1" prefix="">
<DOI name="Mod">
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
</LN>
</LDevice>
</Server>
</AccessPoint>
</IED>
<DataTypeTemplates>
<LNodeType id="MMXU1" lnClass="MMXU">
<DO name="Mod" type="INC_1_Mod" />
<DO name="Beh" type="INS_1_Beh" />
<DO name="Health" type="INS_1_Beh" />
<DO name="NamPlt" type="LPL_2_NamPlt" />
<DO name="TotW" type="MV_1_Vol" />
<DO name="TotVAr" type="MV_1_Vol" />
<DO name="TotVA" type="MV_1_Vol" />
<DO name="Hz" type="MV_1_Vol" />
<DO name="PhV" type="WYE_1_PhV" />
<DO name="A" type="WYE_1_PhV" />
<DO name="W" type="WYE_1_W" />
</LNodeType>
<LNodeType id="LLN02" lnClass="LLN0">
<DO name="Mod" type="INC_1_Mod" />
<DO name="Beh" type="INS_1_Beh" />
<DO name="Health" type="INS_1_Beh" />
<DO name="NamPlt" type="LPL_1_NamPlt" />
</LNodeType>
<LNodeType id="LPHD2" lnClass="LPHD">
<DO name="PhyNam" type="DPL_1_PhyNam" />
<DO name="PhyHealth" type="INS_1_Beh" />
<DO name="Proxy" type="SPS_1_Proxy" />
</LNodeType>
<LNodeType id="ZINV3" lnClass="ZINV">
<DO name="Mod" type="ENC_1_Mod" />
<DO name="Beh" type="ENS_1_Beh" />
<DO name="Health" type="ENS_1_Beh" />
<DO name="NamPlt" type="LPL_2_NamPlt" />
<DO name="WRtg" type="ASG_1_WRtg" />
<DO name="VarRtg" type="ASG_1_WRtg" />
<DO name="ACTyp" type="ENG_1_ACTyp" />
<DO name="OutWSet" type="ASG_1_WRtg" />
<DO name="OutVarSet" type="ASG_1_WRtg" />
</LNodeType>
<DOType id="INC_1_Mod" cdc="INC">
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" type="CtlModels" bType="Enum" fc="CF" />
</DOType>
<DOType id="INS_1_Beh" cdc="INS">
<DA name="stVal" bType="INT32" fc="ST" dchg="true" />
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="LPL_1_NamPlt" cdc="LPL">
<DA name="vendor" bType="VisString255" fc="DC" />
<DA name="swRev" bType="VisString255" fc="DC" />
<DA name="d" bType="VisString255" fc="DC" />
<DA name="configRev" bType="VisString255" fc="DC" />
<DA name="ldNs" bType="VisString255" fc="EX" />
</DOType>
<DOType id="DPL_1_PhyNam" cdc="DPL">
<DA name="vendor" bType="VisString255" fc="DC" />
</DOType>
<DOType id="SPS_1_Proxy" cdc="SPS">
<DA name="stVal" bType="BOOLEAN" fc="ST" dchg="true" />
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="LPL_2_NamPlt" cdc="LPL">
<DA name="vendor" bType="VisString255" fc="DC" />
<DA name="swRev" bType="VisString255" fc="DC" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="ENC_1_Mod" cdc="ENC">
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" type="CtlModels" bType="Enum" fc="CF" />
</DOType>
<DOType id="ENS_1_Beh" cdc="ENS">
<DA name="stVal" bType="INT32" fc="ST" dchg="true" />
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="WYE_1_W" cdc="WYE">
<SDO name="phsA" type="CMV_1_phsA" />
<SDO name="phsB" type="CMV_1_phsA" />
<SDO name="phsC" type="CMV_1_phsA" />
</DOType>
<DOType id="CMV_1_phsA" cdc="CMV">
<DA name="cVal" type="Vector_1" bType="Struct" fc="MX" dchg="true" />
<DA name="q" bType="Quality" fc="MX" qchg="true" />
<DA name="t" bType="Timestamp" fc="MX" />
</DOType>
<DOType id="WYE_1_PhV" cdc="WYE">
<SDO name="phsA" type="CMV_1_phsA" />
<SDO name="phsB" type="CMV_1_phsA" />
<SDO name="phsC" type="CMV_1_phsA" />
<SDO name="neut" type="CMV_1_phsA" />
</DOType>
<DOType id="MV_1_Vol" cdc="MV">
<DA name="mag" type="AnalogueValue_1" bType="Struct" fc="MX" dchg="true" />
<DA name="q" bType="Quality" fc="MX" qchg="true" />
<DA name="t" bType="Timestamp" fc="MX" />
</DOType>
<DOType id="ASG_1_WRtg" cdc="ASG">
<DA name="setMag" type="AnalogueValue_1" bType="Struct" fc="SP" />
<DA name="units" type="Unit_1" bType="Struct" fc="CF" />
</DOType>
<DOType id="ENG_1_ACTyp" cdc="ENG">
<DA name="setVal" bType="INT32" fc="SP" />
</DOType>
<DAType id="AnalogueValue_1">
<BDA name="f" bType="FLOAT32" />
</DAType>
<DAType id="Vector_1">
<BDA name="mag" type="AnalogueValue_1" bType="Struct" />
</DAType>
<DAType id="Unit_1">
<BDA name="SIUnit" type="SIUnit" bType="Enum" />
</DAType>
<EnumType id="CtlModels">
<EnumVal ord="0">status-only</EnumVal>
<EnumVal ord="1">direct-with-normal-security</EnumVal>
<EnumVal ord="2">sbo-with-normal-security</EnumVal>
<EnumVal ord="3">direct-with-enhanced-security</EnumVal>
<EnumVal ord="4">sbo-with-enhanced-security</EnumVal>
</EnumType>
<EnumType id="SIUnit">
<EnumVal ord="1">
</EnumVal>
<EnumVal ord="10">rad</EnumVal>
<EnumVal ord="11">sr</EnumVal>
<EnumVal ord="2">m</EnumVal>
<EnumVal ord="21">Gy</EnumVal>
<EnumVal ord="22">q</EnumVal>
<EnumVal ord="23">ðC</EnumVal>
<EnumVal ord="24">Sv</EnumVal>
<EnumVal ord="25">F</EnumVal>
<EnumVal ord="26">C</EnumVal>
<EnumVal ord="27">S</EnumVal>
<EnumVal ord="28">H</EnumVal>
<EnumVal ord="29">V</EnumVal>
<EnumVal ord="3">kg</EnumVal>
<EnumVal ord="30">ohm</EnumVal>
<EnumVal ord="31">J</EnumVal>
<EnumVal ord="32">N</EnumVal>
<EnumVal ord="33">Hz</EnumVal>
<EnumVal ord="34">Ix</EnumVal>
<EnumVal ord="35">Lm</EnumVal>
<EnumVal ord="36">Wb</EnumVal>
<EnumVal ord="37">T</EnumVal>
<EnumVal ord="38">W</EnumVal>
<EnumVal ord="39">Pa</EnumVal>
<EnumVal ord="4">s</EnumVal>
<EnumVal ord="41">²</EnumVal>
<EnumVal ord="42">³</EnumVal>
<EnumVal ord="43">m/s</EnumVal>
<EnumVal ord="44">m/sò</EnumVal>
<EnumVal ord="45">³/s</EnumVal>
<EnumVal ord="46">m/mó</EnumVal>
<EnumVal ord="47">M</EnumVal>
<EnumVal ord="48">kg/mó</EnumVal>
<EnumVal ord="49">²/s</EnumVal>
<EnumVal ord="5">A</EnumVal>
<EnumVal ord="50">W/m K</EnumVal>
<EnumVal ord="51">J/K</EnumVal>
<EnumVal ord="52">ppm</EnumVal>
<EnumVal ord="53">1/s</EnumVal>
<EnumVal ord="54">rad/s</EnumVal>
<EnumVal ord="6">K</EnumVal>
<EnumVal ord="61">VA</EnumVal>
<EnumVal ord="62">Watts</EnumVal>
<EnumVal ord="63">VAr</EnumVal>
<EnumVal ord="64">theta</EnumVal>
<EnumVal ord="65">cos(theta)</EnumVal>
<EnumVal ord="66">Vs</EnumVal>
<EnumVal ord="67">²</EnumVal>
<EnumVal ord="68">As</EnumVal>
<EnumVal ord="69">²</EnumVal>
<EnumVal ord="7">mol</EnumVal>
<EnumVal ord="70">²t</EnumVal>
<EnumVal ord="71">VAh</EnumVal>
<EnumVal ord="72">Wh</EnumVal>
<EnumVal ord="73">VArh</EnumVal>
<EnumVal ord="74">V/Hz</EnumVal>
<EnumVal ord="8">cd</EnumVal>
<EnumVal ord="9">deg</EnumVal>
</EnumType>
<EnumType id="Multiplier">
<EnumVal ord="-24">Yocto</EnumVal>
<EnumVal ord="-21">Zepto</EnumVal>
<EnumVal ord="-18">Atto</EnumVal>
<EnumVal ord="-15">Femto</EnumVal>
<EnumVal ord="-12">Pico</EnumVal>
<EnumVal ord="-9">Nano</EnumVal>
<EnumVal ord="-6">Micro</EnumVal>
<EnumVal ord="-3">Milli</EnumVal>
<EnumVal ord="-2">Centi</EnumVal>
<EnumVal ord="-1">Deci</EnumVal>
<EnumVal ord="0">zeroNoValue</EnumVal>
<EnumVal ord="1">Deca</EnumVal>
<EnumVal ord="2">Hecto</EnumVal>
<EnumVal ord="3">Kilo</EnumVal>
<EnumVal ord="6">Mega</EnumVal>
<EnumVal ord="9">Giga</EnumVal>
<EnumVal ord="12">Tera</EnumVal>
<EnumVal ord="15">Petra</EnumVal>
<EnumVal ord="18">Exa</EnumVal>
<EnumVal ord="21">Zetta</EnumVal>
<EnumVal ord="24">Yotta</EnumVal>
</EnumType>
<EnumType id="Range">
<EnumVal ord="0">normal</EnumVal>
<EnumVal ord="1">high</EnumVal>
<EnumVal ord="2">low</EnumVal>
<EnumVal ord="3">high-high</EnumVal>
<EnumVal ord="4">low-low</EnumVal>
</EnumType>
</DataTypeTemplates>
</SCL>