You cannot select more than 25 topics Topics must start with a letter or number, can include dashes ('-') and can be up to 35 characters long.
iec61850bean/run-scripts/console-server/sample-model.icd

294 lines
12 KiB
XML

<?xml version="1.0" encoding="UTF-8"?>
<!--This file is generated using Kalkitech SCL Manager IEC61850 Configuration Tool (www.kalkitech.com)-->
<SCL xmlns="http://www.iec.ch/61850/2003/SCL">
<Header id="" version="4.0.2" revision="" toolID="Kalkitech SCL Manager" nameStructure="IEDName" />
<Communication>
<SubNetwork name="subnetwork1" type="8-MMS">
<Text>Station bus</Text>
<BitRate unit="b/s">10</BitRate>
<ConnectedAP iedName="ied1" apName="accessPoint1">
<Address>
<P type="IP">10.0.0.3</P>
<P type="IP-SUBNET">255.255.255.0</P>
<P type="IP-GATEWAY">10.0.0.101</P>
<P type="OSI-TSEL">0001</P>
<P type="OSI-PSEL">00000001</P>
<P type="OSI-SSEL">0001</P>
</Address>
</ConnectedAP>
</SubNetwork>
</Communication>
<IED name="ied1">
<Services>
<DynAssociation />
<GetDirectory />
<GetDataObjectDefinition />
<GetDataSetValue />
<DataSetDirectory />
<ReadWrite />
<GetCBValues />
<ConfLNs fixPrefix="true" fixLnInst="true" />
<GOOSE max="5" />
<GSSE max="5" />
<FileHandling />
<GSEDir />
<TimerActivatedControl />
</Services>
<AccessPoint name="accessPoint1">
<Server>
<Authentication />
<LDevice inst="lDevice1">
<LN0 lnClass="LLN0" lnType="LLN01" inst="">
<DataSet name="dataset1" desc="">
<FCDA ldInst="lDevice1" lnClass="MMXU" fc="MX" lnInst="1" doName="TotW" />
<FCDA ldInst="lDevice1" lnClass="MMXU" fc="MX" lnInst="1" doName="W.phsA" daName="cVal.mag.f" />
</DataSet>
<ReportControl name="urcb1" confRev="0" datSet="dataset1" rptID="urcb1" intgPd="5000" bufTime="0">
<TrgOps dchg="true" qchg="true" dupd="true" period="true" gi="true" />
<OptFields dataSet="true" bufOvfl="false" configRef="true" dataRef="false" entryID="true" reasonCode="true" timeStamp="true" seqNum="true"/>
<RptEnabled max="3"/>
</ReportControl>
<ReportControl name="urcb2" confRev="0" datSet="dataset1" intgPd="0" bufTime="0">
<TrgOps />
<OptFields />
</ReportControl>
<DOI name="Mod">
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
</LN0>
<LN lnClass="LPHD" lnType="LPHD1" inst="1" prefix="" />
<LN lnClass="MMXU" lnType="MMXU1" inst="1" prefix="">
<DOI name="Mod">
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
</LN>
<LN lnClass="CSWI" lnType="CSWI1" inst="1" prefix="">
<DOI name="Mod">
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI name="Pos">
<DAI name="ctlModel">
<Val>direct-with-normal-security</Val>
</DAI>
</DOI>
<DOI name="PosA">
<DAI name="sboTimeout">
<Val>1000</Val>
</DAI>
<DAI name="ctlModel">
<Val>sbo-with-normal-security</Val>
</DAI>
</DOI>
<DOI name="PosB">
<DAI name="ctlModel">
<Val>direct-with-enhanced-security</Val>
</DAI>
</DOI>
<DOI name="PosC">
<DAI name="ctlModel">
<Val>sbo-with-enhanced-security</Val>
</DAI>
</DOI>
</LN>
<LN lnClass="DSCH" lnType="DSCH1" inst="1" prefix="">
<DOI name="Mod">
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
</LN>
</LDevice>
</Server>
</AccessPoint>
</IED>
<DataTypeTemplates>
<LNodeType id="LLN01" lnClass="LLN0">
<DO name="Mod" type="INC_1_Mod" />
<DO name="Beh" type="INS_1_Beh" />
<DO name="Health" type="INS_1_Beh" />
<DO name="NamPlt" type="LPL_1_NamPlt" />
</LNodeType>
<LNodeType id="LPHD1" lnClass="LPHD">
<DO name="PhyNam" type="DPL_1_PhyNam" />
<DO name="PhyHealth" type="INS_1_Beh" />
<DO name="Proxy" type="SPS_1_Proxy" />
</LNodeType>
<LNodeType id="MMXU1" lnClass="MMXU">
<DO name="Mod" type="INC_1_Mod" />
<DO name="Beh" type="INS_1_Beh" />
<DO name="Health" type="INS_1_Beh" />
<DO name="NamPlt" type="LPL_2_NamPlt" />
<DO name="TotW" type="MV_1_TotW" />
<DO name="W" type="WYE_1_W" />
</LNodeType>
<LNodeType id="CSWI1" lnClass="CSWI" desc="Switch controller">
<DO name="Mod" type="INC_1_Mod" />
<DO name="Beh" type="INS_1_Beh" />
<DO name="Health" type="INS_1_Beh" />
<DO name="NamPlt" type="LPL_2_NamPlt" />
<DO name="Pos" type="DPC_1_Pos" />
<DO name="PosA" type="DPC_2_PosA" />
<DO name="PosB" type="DPC_1_PosB" />
<DO name="PosC" type="DPC_1_PosA" />
</LNodeType>
<LNodeType id="DSCH1" lnClass="DSCH" desc="DER energy and/or ancillary services schedule">
<DO name="Mod" type="ENC_1_Mod" />
<DO name="Beh" type="ENS_1_Beh" />
<DO name="Health" type="ENS_1_Beh" />
<DO name="NamPlt" type="LPL_2_NamPlt" />
<DO name="SchdSt" type="INS_1_Beh" />
<DO name="SchdId" type="ING_1_SchdId" />
<DO name="SchdCat" type="ING_1_SchdId" />
<DO name="SchdTyp" type="ING_1_SchdId" />
<DO name="SchdAbsTm" type="SCA_1_SchdAbsTm" />
</LNodeType>
<DOType id="INC_1_Mod" cdc="INC">
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" type="CtlModels" bType="Enum" fc="CF" />
</DOType>
<DOType id="INS_1_Beh" cdc="INS">
<DA name="stVal" bType="INT32" fc="ST" dchg="true" />
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="LPL_1_NamPlt" cdc="LPL">
<DA name="vendor" bType="VisString255" fc="DC" />
<DA name="swRev" bType="VisString255" fc="DC" />
<DA name="d" bType="VisString255" fc="DC" />
<DA name="configRev" bType="VisString255" fc="DC" />
<DA name="ldNs" bType="VisString255" fc="EX" />
</DOType>
<DOType id="DPL_1_PhyNam" cdc="DPL">
<DA name="vendor" bType="VisString255" fc="DC" />
</DOType>
<DOType id="SPS_1_Proxy" cdc="SPS">
<DA name="stVal" bType="BOOLEAN" fc="ST" dchg="true" />
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="LPL_2_NamPlt" cdc="LPL">
<DA name="vendor" bType="VisString255" fc="DC" />
<DA name="swRev" bType="VisString255" fc="DC" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="MV_1_TotW" cdc="MV">
<DA name="mag" type="AnalogueValue_1" bType="Struct" fc="MX" dchg="true" dupd="true" />
<DA name="q" bType="Quality" fc="MX" qchg="true" />
<DA name="t" bType="Timestamp" fc="MX" />
</DOType>
<DOType id="WYE_1_W" cdc="WYE">
<SDO name="phsA" type="CMV_1_phsA" />
<SDO name="phsB" type="CMV_1_phsA" />
<SDO name="phsC" type="CMV_1_phsA" />
</DOType>
<DOType id="CMV_1_phsA" cdc="CMV">
<DA name="cVal" type="Vector_1" bType="Struct" fc="MX" dchg="true" />
<DA name="q" bType="Quality" fc="MX" qchg="true" />
<DA name="t" bType="Timestamp" fc="MX" />
</DOType>
<DOType id="DPC_1_Pos" cdc="DPC">
<DA name="Oper" type="DPCSelectWithValue_1" bType="Struct" fc="CO" />
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" type="CtlModels" bType="Enum" fc="CF" />
</DOType>
<DOType id="DPC_2_PosA" cdc="DPC">
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" type="CtlModels" bType="Enum" fc="CF" />
<DA name="sboTimeout" bType="INT32U" fc="CF" />
<DA name="SBO" bType="VisString64" fc="CO" />
<DA name="Oper" type="DPCOperate_1" bType="Struct" fc="CO" />
<DA name="Cancel" type="DPCCancel_1" bType="Struct" fc="CO" />
</DOType>
<DOType id="DPC_1_PosB" cdc="DPC">
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" type="CtlModels" bType="Enum" fc="CF" />
<DA name="Oper" type="DPCOperate_1" bType="Struct" fc="CO" />
<DA name="Cancel" type="DPCCancel_1" bType="Struct" fc="CO" />
</DOType>
<DOType id="DPC_1_PosA" cdc="DPC">
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" type="CtlModels" bType="Enum" fc="CF" />
<DA name="SBOw" type="DPCSelectWithValue_1" bType="Struct" fc="CO" />
<DA name="Oper" type="DPCOperate_1" bType="Struct" fc="CO" />
<DA name="Cancel" type="DPCCancel_1" bType="Struct" fc="CO" />
</DOType>
<DOType id="ENC_1_Mod" cdc="ENC">
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" type="CtlModels" bType="Enum" fc="CF" />
</DOType>
<DOType id="ENS_1_Beh" cdc="ENS">
<DA name="stVal" bType="INT32" fc="ST" dchg="true" />
<DA name="q" bType="Quality" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="ING_1_SchdId" cdc="ING" />
<DOType id="SCA_1_SchdAbsTm" cdc="SCA">
<DA name="val" bType="FLOAT32" count="24" fc="SP" dchg="true" />
</DOType>
<DAType id="AnalogueValue_1">
<BDA name="f" bType="FLOAT32" />
</DAType>
<DAType id="Vector_1">
<BDA name="mag" type="AnalogueValue_1" bType="Struct" />
</DAType>
<DAType id="DPCSelectWithValue_1">
<BDA name="ctlVal" bType="BOOLEAN" />
<BDA name="origin" type="Originator_1" bType="Struct" />
<BDA name="ctlNum" bType="INT8U" />
<BDA name="T" bType="Timestamp" />
<BDA name="Test" bType="BOOLEAN" />
<BDA name="Check" bType="Check" />
</DAType>
<DAType id="Originator_1">
<BDA name="orCat" type="OrCat" bType="Enum" />
<BDA name="orIdent" bType="Octet64" />
</DAType>
<DAType id="DPCOperate_1">
<BDA name="ctlVal" bType="BOOLEAN" />
<BDA name="origin" type="Originator_1" bType="Struct" />
<BDA name="ctlNum" bType="INT8U" />
<BDA name="T" bType="Timestamp" />
<BDA name="Test" bType="BOOLEAN" />
<BDA name="Check" bType="Check" />
</DAType>
<DAType id="DPCCancel_1">
<BDA name="ctlVal" bType="BOOLEAN" />
<BDA name="origin" type="Originator_1" bType="Struct" />
<BDA name="ctlNum" bType="INT8U" />
<BDA name="T" bType="Timestamp" />
<BDA name="Test" bType="BOOLEAN" />
</DAType>
<EnumType id="CtlModels">
<EnumVal ord="0">status-only</EnumVal>
<EnumVal ord="1">direct-with-normal-security</EnumVal>
<EnumVal ord="2">sbo-with-normal-security</EnumVal>
<EnumVal ord="3">direct-with-enhanced-security</EnumVal>
<EnumVal ord="4">sbo-with-enhanced-security</EnumVal>
</EnumType>
<EnumType id="OrCat">
<EnumVal ord="0">not-supported</EnumVal>
<EnumVal ord="1">bay-control</EnumVal>
<EnumVal ord="2">station-control</EnumVal>
<EnumVal ord="3">remote-control</EnumVal>
<EnumVal ord="4">automatic-bay</EnumVal>
<EnumVal ord="5">automatic-station</EnumVal>
<EnumVal ord="6">automatic-remote</EnumVal>
<EnumVal ord="7">maintenance</EnumVal>
<EnumVal ord="8">process</EnumVal>
</EnumType>
</DataTypeTemplates>
</SCL>